siemens 7SK80
7SK80
Importata da documento
| Len | Scala | Endian | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| 30001 | Ia Corrente di fase A. | ia | 4 | int16 | 1 | 0.1 | A | R | — | |
| 40001 | Hardware designation of the communication module 8 registri (stringa max 16 caratteri). "AME-GEN" per modulo AME, "AMO-GEN" per modulo AMO. | hardware_designation_of_the_communication_module | 3 | string | — | 1 | — | R | — | |
| 1 | 52 Breaker ON Comando doppio con indicazione di ritorno (checkback) sulla stessa posizione. | 52_breaker_on | 1 | boolean | 1 | 1 | — | R/W | — | |
| 30002 | Ib Corrente di fase B. | ib | 4 | int16 | 1 | 0.1 | A | R | — | |
| 2 | 52 Breaker OFF Comando doppio con indicazione di ritorno (checkback) sulla stessa posizione. | 52_breaker_off | 1 | boolean | 1 | 1 | — | R/W | — | |
| 30003 | Ic Corrente di fase C. | ic | 4 | int16 | 1 | 0.1 | A | R | — | |
| 30004 | In Corrente di neutro. | in | 4 | int16 | 1 | 0.1 | A | R | — | |
| 30005 | Va | va | 4 | int16 | 1 | 0.01 | kV | R | — | |
| 30006 | Vb | vb | 4 | int16 | 1 | 0.01 | kV | R | — | |
| 30007 | Vc | vc | 4 | int16 | 1 | 0.01 | kV | R | — | |
| 30008 | Va-b | va_b | 4 | int16 | 1 | 0.01 | kV | R | — | |
| 30009 | Vb-c | vb_c | 4 | int16 | 1 | 0.01 | kV | R | — | |
| 40009 | Communication module software revision (major) MSB della revisione firmware del modulo di comunicazione. Es.: reg 40009=0001H, reg 40010=0205H -> Revisione 1.2.5. | communication_module_software_revision_major | 3 | uint16 | 1 | 1 | — | R | — | |
| 30010 | Vc-a | vc_a | 4 | int16 | 1 | 0.01 | kV | R | — | |
| 40010 | Communication module software revision (minor.patch) LSB della revisione firmware del modulo di comunicazione, vedi 40009. | communication_module_software_revision_minor_patch | 3 | uint16 | 1 | 1 | — | R | — | |
| 30011 | VN | vn | 4 | int16 | 1 | 0.01 | kV | R | — | |
| 40011 | MLFB (order number) of the SIPROTEC device 16 registri (stringa max 32 caratteri). Es.: "7SJ80115EA903FA3----0D----------". | mlfb_order_number_of_the_siprotec_device | 3 | string | — | 1 | — | R | — | |
| 30012 | P Potenza attiva. | p | 4 | int16 | 1 | 0.01 | MW | R | — | |
| 30013 | Q Potenza reattiva. | q | 4 | int16 | 1 | 0.01 | MVAR | R | — | |
| 30014 | S Potenza apparente. | s | 4 | int16 | 1 | 0.01 | MVA | R | — | |
| 30015 | Freq | freq | 4 | int16 | 1 | 0.01 | Hz | R | — | |
| 30016 | PF Power Factor. Scala 3.2767/32767. | pf | 4 | int16 | 1 | 0.0001 | — | R | — | |
| 40027 | Date and time of mapping data generation 8 registri (stringa max 16 caratteri). Es.: "140106095747330" = 14 gen 2006, 09:57:47.330. | date_and_time_of_mapping_data_generation | 3 | string | — | 1 | — | R | — | |
| 10034 | 50/51 PH ACT 1 = 50/51 O/C is ACTIVE | 50_51_ph_act | 2 | boolean | 1 | 1 | — | R | — | |
| 40035 | Number of selected standard mapping MSB=numero mapping standard selezionato, LSB=byte alto della revisione mapping (continua nel registro 40036). Es.: reg 40035=3102H, reg 40036=0304H -> Standard mapping 3-1, Revisione 2.3.4. | number_of_selected_standard_mapping | 3 | uint16 | 1 | 1 | — | R | — | |
| 10035 | 50N/51N ACT 1 = 50N/51N is ACTIVE | 50n_51n_act | 2 | boolean | 1 | 1 | — | R | — | |
| 40036 | Revision of mapping data (low word) Completa la codifica della revisione del mapping, vedi 40035. | revision_of_mapping_data_low_word | 3 | uint16 | 1 | 1 | — | R | — | |
| 10036 | 50(N)/51(N) PU 1 = 50(N)/51(N) O/C PICKUP | 50_n_51_n_pu | 2 | boolean | 1 | 1 | — | R | — | |
| 10037 | 50/51 Ph A PU 1 = 50/51 Phase A picked up | 50_51_ph_a_pu | 2 | boolean | 1 | 1 | — | R | — | |
| 10038 | 50/51 Ph B PU 1 = 50/51 Phase B picked up | 50_51_ph_b_pu | 2 | boolean | 1 | 1 | — | R | — | |
| 10039 | 50/51 Ph C PU 1 = 50/51 Phase C picked up | 50_51_ph_c_pu | 2 | boolean | 1 | 1 | — | R | — | |
| 10040 | 50N/51N Pickedup 1 = 50N/51N picked up | 50n_51n_pickedup | 2 | boolean | 1 | 1 | — | R | — | |
| 10041 | 50(N)/51(N) TRIP 1 = 50(N)/51(N) TRIP | 50_n_51_n_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 10042 | PhA InrushBlk 1 = Phase A trip blocked by inrush detection | pha_inrushblk | 2 | boolean | 1 | 1 | — | R | — | |
| 10043 | PhB InrushBlk 1 = Phase B trip blocked by inrush detection | phb_inrushblk | 2 | boolean | 1 | 1 | — | R | — | |
| 10044 | PhC InrushBlk 1 = Phase C trip blocked by inrush detection | phc_inrushblk | 2 | boolean | 1 | 1 | — | R | — | |
| 44 | Mode REMOTE Comando+indicazione sulla stessa posizione. 0=Set to LOCKED / LOCKED, 1=Set to UNLOCKED / UNLOCKED. Se non arriva nessun comando Modbus entro 5 minuti dallo sblocco, il dispositivo si riblocca automaticamente su LOCKED. | mode_remote | 1 | boolean | 1 | 1 | — | R/W | — | |
| 10045 | INRUSH X-BLK 1 = Cross blk: PhX blocked PhY | inrush_x_blk | 2 | boolean | 1 | 1 | — | R | — | |
| 45 | Setting Group A Comando+indicazione sulla stessa posizione. Scrivere 1 attiva il gruppo di parametri A (disattiva automaticamente quello attivo); scrivere 0 e' rifiutato. Richiede il parametro "Change to Another Setting Group"=Protocol. | setting_group_a | 1 | boolean | 1 | 1 | — | R/W | — | |
| 10046 | 67 ACTIVE 1 = 67/67-TOC is ACTIVE | 67_active | 2 | boolean | 1 | 1 | — | R | — | |
| 46 | Setting Group B Comando+indicazione sulla stessa posizione. Vedi Setting Group A per il comportamento di attivazione. | setting_group_b | 1 | boolean | 1 | 1 | — | R/W | — | |
| 10047 | 67N ACTIVE 1 = 67N/67N-TOC is ACTIVE | 67n_active | 2 | boolean | 1 | 1 | — | R | — | |
| 47 | Setting Group C Comando+indicazione sulla stessa posizione. Vedi Setting Group A per il comportamento di attivazione. | setting_group_c | 1 | boolean | 1 | 1 | — | R/W | — | |
| 10048 | 67/67N pickedup 1 = 67/67N picked up | 67_67n_pickedup | 2 | boolean | 1 | 1 | — | R | — | |
| 48 | Setting Group D Comando+indicazione sulla stessa posizione. Vedi Setting Group A per il comportamento di attivazione. | setting_group_d | 1 | boolean | 1 | 1 | — | R/W | — | |
| 10049 | 67 A picked up 1 = 67/67-TOC Phase A picked up | 67_a_picked_up | 2 | boolean | 1 | 1 | — | R | — | |
| 10050 | 67 B picked up 1 = 67/67-TOC Phase B picked up | 67_b_picked_up | 2 | boolean | 1 | 1 | — | R | — | |
| 10051 | 67 C picked up 1 = 67/67-TOC Phase C picked up | 67_c_picked_up | 2 | boolean | 1 | 1 | — | R | — | |
| 10052 | 67N picked up 1 = 67N/67N-TOC picked up | 67n_picked_up | 2 | boolean | 1 | 1 | — | R | — | |
| 10053 | 67/67N TRIP 1 = 67/67N TRIP | 67_67n_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 10054 | 46 ACTIVE 1 = 46 is ACTIVE | 46_active | 2 | boolean | 1 | 1 | — | R | — | |
| 10055 | 46-2 picked up 1 = 46-2 picked up | 46_2_picked_up | 2 | boolean | 1 | 1 | — | R | — | |
| 10056 | 46-1 picked up 1 = 46-1 picked up | 46_1_picked_up | 2 | boolean | 1 | 1 | — | R | — | |
| 10057 | 46-TOC pickedup 1 = 46-TOC picked up | 46_toc_pickedup | 2 | boolean | 1 | 1 | — | R | — | |
| 10058 | 46 TRIP 1 = 46 TRIP | 46_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 10059 | 81 ACTIVE 1 = 81 is ACTIVE | 81_active | 2 | boolean | 1 | 1 | — | R | — | |
| 10060 | 81-1 picked up 1 = 81-1 picked up | 81_1_picked_up | 2 | boolean | 1 | 1 | — | R | — | |
| 10061 | 81-2 picked up 1 = 81-2 picked up | 81_2_picked_up | 2 | boolean | 1 | 1 | — | R | — | |
| 10062 | 81-1 TRIP 1 = 81-1 TRIP | 81_1_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 10063 | 81-2 TRIP 1 = 81-2 TRIP | 81_2_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 10064 | 27 ACTIVE 1 = 27 Undervoltage protection is ACTIVE | 27_active | 2 | boolean | 1 | 1 | — | R | — | |
| 40065 | Milliseconds Registro di trasferimento data/ora. | milliseconds | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 10065 | 27-1 picked up 1 = 27-1 Undervoltage picked up | 27_1_picked_up | 2 | boolean | 1 | 1 | — | R | — | |
| 40066 | Hours / Minutes Byte alto=Ore, byte basso=Minuti. | hours_minutes | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 10066 | 27-1 TRIP 1 = 27-1 Undervoltage TRIP | 27_1_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 40067 | Month / Day Byte alto=Mese, byte basso=Giorno. | month_day | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 10067 | 59 ACTIVE 1 = 59-Overvoltage protection is ACTIVE | 59_active | 2 | boolean | 1 | 1 | — | R | — | |
| 40068 | Time/Date status byte / Year Byte alto=byte di stato data/ora, byte basso=Anno. | time_date_status_byte_year | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 10068 | 59-1 picked up 1 = 59 picked up | 59_1_picked_up | 2 | boolean | 1 | 1 | — | R | — | |
| 40069 | Set Time and Date Disponibile solo se la sincronizzazione oraria e' configurata con l'uso di questo registro. | set_time_and_date | 6 | uint16 | 1 | 1 | — | W | — | |
| 10069 | 59-1 TRIP 1 = 59 TRIP | 59_1_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 10070 | 50Ns/67Ns ACT 1 = 50Ns/67Ns is ACTIVE | 50ns_67ns_act | 2 | boolean | 1 | 1 | — | R | — | |
| 10071 | 64 Pickup 1 = 64 displacement voltage pick up | 64_pickup | 2 | boolean | 1 | 1 | — | R | — | |
| 10072 | 64 TRIP 1 = 64 displacement voltage element TRIP | 64_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 10073 | 50Ns-2 Pickup 1 = 50Ns-2 Pickup | 50ns_2_pickup | 2 | boolean | 1 | 1 | — | R | — | |
| 10074 | 50Ns-2 TRIP 1 = 50Ns-2 TRIP | 50ns_2_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 10075 | 50Ns-1 Pickup 1 = 50Ns-1 Pickup | 50ns_1_pickup | 2 | boolean | 1 | 1 | — | R | — | |
| 10076 | 50Ns-1 TRIP 1 = 50Ns-1 TRIP | 50ns_1_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 10077 | Sens. Gnd Ph A 1 = Sensitive ground fault picked up in phase A | sens_gnd_ph_a | 2 | boolean | 1 | 1 | — | R | — | |
| 10078 | Sens. Gnd Ph B 1 = Sensitive ground fault picked up in phase B | sens_gnd_ph_b | 2 | boolean | 1 | 1 | — | R | — | |
| 10079 | Sens. Gnd Ph C 1 = Sensitive ground fault picked up in phase C | sens_gnd_ph_c | 2 | boolean | 1 | 1 | — | R | — | |
| 10080 | SensGnd Forward 1 = Sensitive ground fault in forward direction | sensgnd_forward | 2 | boolean | 1 | 1 | — | R | — | |
| 10081 | SensGnd Reverse 1 = Sensitive ground fault in reverse direction | sensgnd_reverse | 2 | boolean | 1 | 1 | — | R | — | |
| 10082 | 66 ACTIVE 1 = 66 Motor start protection is ACTIVE | 66_active | 2 | boolean | 1 | 1 | — | R | — | |
| 10083 | 66 TRIP 1 = 66 Motor start protection TRIP | 66_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 10084 | START-SUP ACT 1 = Startup supervision is ACTIVE | start_sup_act | 2 | boolean | 1 | 1 | — | R | — | |
| 10085 | START-SUP TRIP 1 = Startup supervision TRIP | start_sup_trip | 2 | boolean | 1 | 1 | — | R | — | |
| 10086 | START-SUP pu 1 = Startup supervision Pickup | start_sup_pu | 2 | boolean | 1 | 1 | — | R | — | |
| 10087 | 74TC ACTIVE 1 = 74TC Trip circuit supervision is ACTIVE | 74tc_active | 2 | boolean | 1 | 1 | — | R | — | |
| 10088 | FAIL: Trip cir. 1 = 74TC Failure Trip Circuit | fail_trip_cir | 2 | boolean | 1 | 1 | — | R | — | |
| 10089 | Cntrl Auth 1 = Control authority (0=REMOTE, 1=LOCAL) | cntrl_auth | 2 | boolean | 1 | 1 | — | R | — | |
| 10090 | ModeLOCAL 1 = Control mode LOCAL (0=LOCKED, 1=UNLOCKED) | modelocal | 2 | boolean | 1 | 1 | — | R | — | |
| 40129 | Diagnostics word bit0 Device OK(1=aggiornamento della replica del dispositivo completato dopo avvio/riavvio); bit1 Settings Calc.(1=calcolo impostazioni in corso); bit2 ProtActive(1=almeno una funzione di protezione attiva); bit3 Error Sum Alarm(1=allarme sommario di errore attivo); bit4 Alarm Sum Event(1=evento sommario di allarme attivo); bit5 Relay PICKUP(1=segnale di gruppo PICKUP); bit6 Relay TRIP(1=comando TRIP generale); bit8 Test mode(1=modalita' test attiva); bit15 Data invalid(1=dati nel messaggio Modbus non validi, generata dallo slave Modbus). Leggibile anche con funzione Diagnostics(FC8), sottofunzione Return Diagnostic Register. | diagnostics_word | 3 | bitfield | 1 | 1 | — | R | — | |
| 40201 | Wp(puls) - Pulsed Energy Wp (active) Impulsi di energia attiva contati su ingresso binario. Scala: 2^31-1 impulsi = fondo scala. Riferimento: 60000 impulsi/ora per V=Vnom e I=Inom (parametri 1101/1102). | wp_puls_pulsed_energy_wp_active | 3 | uint32 | 2 | 1 | — | R | — | |
| 40203 | Wq(puls) - Pulsed Energy Wq (reactive) Impulsi di energia reattiva contati su ingresso binario. Vedi 40201 per la scala di riferimento. | wq_puls_pulsed_energy_wq_reactive | 3 | uint32 | 2 | 1 | — | R | — | |
| 40205 | WpForward - Wp Forward Energia attiva contatore derivato dai valori misurati. Vedi 40201 per la scala di riferimento. | wpforward_wp_forward | 3 | uint32 | 2 | 1 | — | R | — | |
| 40207 | WqForward - Wq Forward Energia reattiva contatore derivato dai valori misurati. Vedi 40201 per la scala di riferimento. | wqforward_wq_forward | 3 | uint32 | 2 | 1 | — | R | — | |
| 40209 | WpReverse - Wp Reverse Energia attiva inversa, contatore derivato dai valori misurati. Vedi 40201 per la scala di riferimento. | wpreverse_wp_reverse | 3 | uint32 | 2 | 1 | — | R | — | |
| 40211 | WqReverse - Wq Reverse Energia reattiva inversa, contatore derivato dai valori misurati. Vedi 40201 per la scala di riferimento. | wqreverse_wq_reverse | 3 | uint32 | 2 | 1 | — | R | — | |
| 40301 | Ia - Primary fault current | ia_primary_fault_current | 3 | uint32 | 2 | 0.01 | kA | R | — | |
| 40303 | Ib - Primary fault current | ib_primary_fault_current | 3 | uint32 | 2 | 0.01 | kA | R | — | |
| 40305 | Ic - Primary fault current | ic_primary_fault_current | 3 | uint32 | 2 | 0.01 | kA | R | — | |
| 40311 | Sum Ia - Accumulation of interrupted current Ph A | sum_ia_accumulation_of_interrupted_current_ph_a | 3 | uint32 | 2 | 0.01 | kA | R | — | |
| 40313 | Sum Ib - Accumulation of interrupted current Ph B | sum_ib_accumulation_of_interrupted_current_ph_b | 3 | uint32 | 2 | 0.01 | kA | R | — | |
| 40315 | Sum Ic - Accumulation of interrupted current Ph C | sum_ic_accumulation_of_interrupted_current_ph_c | 3 | uint32 | 2 | 0.01 | kA | R | — | |
| 40317 | Op.Hours - Counter of operating hours | op_hours_counter_of_operating_hours | 3 | uint32 | 2 | 1 | h | R | — | |
| 40351 | Ia Min Seguito da 4 registri con data/ora dell'evento (non importati). | ia_min | 3 | int16 | 1 | 0.1 | A | R | — | |
| 40356 | Ia Max Seguito da 4 registri con data/ora dell'evento (non importati). | ia_max | 3 | int16 | 1 | 0.1 | A | R | — | |
| 40361 | Ib Min Seguito da 4 registri con data/ora dell'evento (non importati). | ib_min | 3 | int16 | 1 | 0.1 | A | R | — | |
| 40366 | Ib Max Seguito da 4 registri con data/ora dell'evento (non importati). | ib_max | 3 | int16 | 1 | 0.1 | A | R | — | |
| 40371 | Ic Min Seguito da 4 registri con data/ora dell'evento (non importati). | ic_min | 3 | int16 | 1 | 0.1 | A | R | — | |
| 40376 | Ic Max Seguito da 4 registri con data/ora dell'evento (non importati). | ic_max | 3 | int16 | 1 | 0.1 | A | R | — | |
| 40381 | Va-nMin Seguito da 4 registri con data/ora dell'evento (non importati). | va_nmin | 3 | int16 | 1 | 0.01 | kV | R | — | |
| 40386 | Va-nMax Seguito da 4 registri con data/ora dell'evento (non importati). | va_nmax | 3 | int16 | 1 | 0.01 | kV | R | — | |
| 40391 | Vb-nMin Seguito da 4 registri con data/ora dell'evento (non importati). | vb_nmin | 3 | int16 | 1 | 0.01 | kV | R | — | |
| 40396 | Vb-nMax Seguito da 4 registri con data/ora dell'evento (non importati). | vb_nmax | 3 | int16 | 1 | 0.01 | kV | R | — | |
| 40401 | Vc-nMin Seguito da 4 registri con data/ora dell'evento (non importati). | vc_nmin | 3 | int16 | 1 | 0.01 | kV | R | — | |
| 40406 | Vc-nMax Seguito da 4 registri con data/ora dell'evento (non importati). | vc_nmax | 3 | int16 | 1 | 0.01 | kV | R | — | |
| 40411 | Vn Min V neutro. Seguito da 4 registri con data/ora dell'evento (non importati). | vn_min | 3 | int16 | 1 | 0.01 | kV | R | — | |
| 40416 | Vn Max V neutro. Seguito da 4 registri con data/ora dell'evento (non importati). | vn_max | 3 | int16 | 1 | 0.01 | kV | R | — | |
| 40421 | Pmin Potenza attiva minima. Seguito da 4 registri con data/ora dell'evento (non importati). | pmin | 3 | int16 | 1 | 0.01 | MW | R | — | |
| 40426 | Pmax Potenza attiva massima. Seguito da 4 registri con data/ora dell'evento (non importati). | pmax | 3 | int16 | 1 | 0.01 | MW | R | — | |
| 40431 | Qmin Potenza reattiva minima. Seguito da 4 registri con data/ora dell'evento (non importati). | qmin | 3 | int16 | 1 | 0.01 | MVAR | R | — | |
| 40436 | Qmax Potenza reattiva massima. Seguito da 4 registri con data/ora dell'evento (non importati). | qmax | 3 | int16 | 1 | 0.01 | MVAR | R | — | |
| 40441 | Smin Potenza apparente minima. Seguito da 4 registri con data/ora dell'evento (non importati). | smin | 3 | int16 | 1 | 0.01 | MVA | R | — | |
| 40446 | Smax Potenza apparente massima. Seguito da 4 registri con data/ora dell'evento (non importati). | smax | 3 | int16 | 1 | 0.01 | MVA | R | — | |
| 40451 | fmin Frequenza minima. Seguito da 4 registri con data/ora dell'evento (non importati). | fmin | 3 | int16 | 1 | 0.01 | Hz | R | — | |
| 40456 | fmax Frequenza massima. Seguito da 4 registri con data/ora dell'evento (non importati). | fmax | 3 | int16 | 1 | 0.01 | Hz | R | — | |
| 40461 | PF Min Power Factor minimo. ATTENZIONE: il documento riporta la scala come "3.767" (anziche' "3.2767" come per PF Max): probabile refuso, riportato cosi' com'e' senza correggere. Seguito da 4 registri con data/ora dell'evento (non importati). | pf_min | 3 | int16 | 1 | 0.000115 | — | R | — | |
| 40466 | PF Max Power Factor massimo. Scala 3.2767/32767. Seguito da 4 registri con data/ora dell'evento (non importati). | pf_max | 3 | int16 | 1 | 0.0001 | — | R | — |
Leggi questi registri via API