Legrand CS102

CS102

Importata da documento

Mappa registri Modbus

94 registri

LenScalaEndian
0
Battery Status
1=unknown, 2=battery normal, 3=battery low, 4=battery depleted, 5=battery discharging, 6=battery failure.
battery_status4uint1611—R—
0
Battery Bad
battery_bad2boolean11—R—
0
Config Input Voltage
config_input_voltage3uint1611VR/W—
1
Seconds On Battery
seconds_on_battery4uint3221sR—
1
On Battery
on_battery2boolean11—R—
1
Config Input Frequency
config_input_frequency3uint1611HzR/W—
2
Low Battery
low_battery2boolean11—R—
2
Config Output Voltage
config_output_voltage3uint1611VR/W—
3
Estimated Minutes Remaining
estimated_minutes_remaining4uint1611minR—
3
Battery Depleted
battery_depleted2boolean11—R—
3
Config Output Frequency
config_output_frequency3uint1611HzR/W—
4
Estimated Charge Remaining
estimated_charge_remaining4uint1611%R—
4
Over Temperature
over_temperature2boolean11—R—
4
Config Output Apparent Power
config_output_apparent_power3uint3221VAR—
5
Battery Voltage
battery_voltage4uint1610.1VR—
5
Input Bad
input_bad2boolean11—R—
6
Battery Current
battery_current4uint1610.1AR—
6
Output Bad
output_bad2boolean11—R—
6
Config Output Active Power
config_output_active_power3uint3221WR—
7
UPS Temperature
ups_temperature4uint1610.1°CR—
7
Output Overload
output_overload2boolean11—R—
8
On Bypass
on_bypass2boolean11—R—
8
Config Low Voltage Transfer Point
config_low_voltage_transfer_point3uint1611VR/W—
9
Bypass Bad
bypass_bad2boolean11—R—
9
Config High Voltage Transfer Point
config_high_voltage_transfer_point3uint1611VR/W—
10
Config Over Temperature Set Point (°F)
Range: 50~212. Nome duplicato nel documento originale rispetto a 0x000E (stesso dato in °C): indirizzo diverso, mantenuti entrambi.
config_over_temperature_set_point_f3uint1611°FR/W—
12
Charger Failed
charger_failed2boolean11—R—
12
Config Low Battery Time
config_low_battery_time3uint1611minR/W—
13
Config Audible Status
1=disabled, 2=enabled, 3=muted.
config_audible_status3uint1611—R/W—
14
Config Over Temperature Set Point (°C)
Range: 10~100. Nome duplicato nel documento originale rispetto a 0x000A (stesso dato in °F): indirizzo diverso, mantenuti entrambi.
config_over_temperature_set_point_c3uint1611°CR/W—
15
Fan Failure
fan_failure2boolean11—R—
16
Input Line Bad
Contatore.
input_line_bad4uint1611—R—
16
Fuse Failure
fuse_failure2boolean11—R—
16
Shutdown Type
1=output, 2=system.
shutdown_type3uint1611—R/W—
17
Input Number of Lines
input_number_of_lines4uint1611—R—
17
General Fault
general_fault2boolean11—R—
17
Shutdown After Delay
shutdown_after_delay3uint3221sR/W—
18
Input Frequency phase 1
input_frequency_phase_14uint1610.1HzR—
18
Diagnostic Test Failed
diagnostic_test_failed2boolean11—R—
19
Input Frequency phase 2
input_frequency_phase_24uint1610.1HzR—
19
Communications Lost
communications_lost2boolean11—R—
19
Startup After Delay
startup_after_delay3uint3221sR/W—
20
Input Frequency phase 3
input_frequency_phase_34uint1610.1HzR—
21
Input Voltage phase 1
input_voltage_phase_14uint1610.1VR—
21
Reboot After Delay
Range: 1~300.
reboot_after_delay3uint3221sR/W—
22
Input Voltage phase 2
input_voltage_phase_24uint1610.1VR—
23
Input Voltage phase 3
input_voltage_phase_34uint1610.1VR—
23
Test In Progress
test_in_progress2boolean11—R—
23
Auto Restart Action
1=on, 2=off.
auto_restart_action3uint1611—R/W—
24
Input Current phase 1
input_current_phase_14uint1610.1AR—
24
Ups Sleep Time Setting
Range: 0~10000.
ups_sleep_time_setting3uint1611minR/W—
25
Input Current phase 2
input_current_phase_24uint1610.1AR—
25
Ups Control Setting
1=turn off UPS, 2=put UPS to sleep mode, 3=turn on UPS/cancel shutdown, 4=none (default).
ups_control_setting3uint1611—R/W—
26
Input Current phase 3
input_current_phase_34uint1610.1AR—
26
UPS Shutdown Delay
ups_shutdown_delay3uint1611sR/W—
27
Input Active Power phase 1
input_active_power_phase_14uint3221WR—
29
Input Active Power phase 2
input_active_power_phase_24uint3221WR—
31
Input Active Power phase 3
input_active_power_phase_34uint3221WR—
48
Output Source
1=other, 2=none, 3=normal, 4=bypass, 5=battery, 6=booster, 7=reducer.
output_source4uint1611—R—
48
Battery Test Action
0=none (default), 1=quick battery test, 2=battery test until battery low, 3=timed battery test, 4=cancel active battery test, 5=clear last battery test results.
battery_test_action3uint1611—R/W—
49
Output Number Lines
output_number_lines4uint1611—R—
49
Battery Test Setting Time (Control)
Nome duplicato nel documento originale rispetto a 0x0070 del gruppo Tests: indirizzo diverso, mantenuti entrambi.
battery_test_setting_time_control3uint1611minR/W—
50
Output Frequency phase 1
output_frequency_phase_14uint1610.1HzR—
53
Output Voltage phase 1
output_voltage_phase_14uint1610.1VR—
54
Output Voltage phase 2
output_voltage_phase_24uint1610.1VR—
55
Output Voltage phase 3
output_voltage_phase_34uint1610.1VR—
56
Output Current phase 1
output_current_phase_14uint1610.1AR—
57
Output Current phase 2
output_current_phase_24uint1610.1AR—
58
Output Current phase 3
output_current_phase_34uint1610.1AR—
59
Output Active Power phase 1
output_active_power_phase_14uint3221WR—
61
Output Active Power phase 2
output_active_power_phase_24uint3221WR—
63
Output Active Power phase 3
output_active_power_phase_34uint3221WR—
65
Output Percent Load phase 1
output_percent_load_phase_14uint1610.1%R—
66
Output Percent Load phase 2
output_percent_load_phase_24uint1610.1%R—
67
Output Percent Load phase 3
output_percent_load_phase_34uint1610.1%R—
68
Output Apparent Power phase 1
output_apparent_power_phase_14uint3221VAR—
70
Output Apparent Power phase 2
output_apparent_power_phase_24uint3221VAR—
72
Output Apparent Power phase 3
output_apparent_power_phase_34uint3221VAR—
80
Bypass Number Lines
bypass_number_lines4uint1611—R—
81
Bypass Frequency phase 1
bypass_frequency_phase_14uint1610.1HzR—
84
Bypass Voltage phase 1
bypass_voltage_phase_14uint1610.1VR—
85
Bypass Voltage phase 2
bypass_voltage_phase_24uint1610.1VR—
86
Bypass Voltage phase 3
bypass_voltage_phase_34uint1610.1VR—
87
Bypass Current phase 1
bypass_current_phase_14uint1610.1AR—
88
Bypass Current phase 2
bypass_current_phase_24uint1610.1AR—
89
Bypass Current phase 3
bypass_current_phase_34uint1610.1AR—
90
Bypass Active Power phase 1
bypass_active_power_phase_14uint3221WR—
92
Bypass Active Power phase 2
bypass_active_power_phase_24uint3221WR—
94
Bypass Active Power phase 3
bypass_active_power_phase_34uint3221WR—
112
Battery Test Setting Time (Tests)
Nome duplicato nel documento originale rispetto a 0x0031 del gruppo Control: indirizzo diverso, mantenuti entrambi.
battery_test_setting_time_tests3uint1611minR/W—
113
Battery Test Result
1=done passed, 2=done warning, 4=aborted, 5=in progress, 6=no test initiated (default).
battery_test_result3uint1611—R—
114
Battery Test Start Time
Timestamp.
battery_test_start_time3uint3221—R—
116
Battery Test Elapsed Time
Timeticks.
battery_test_elapsed_time3uint3221—R—
145
UPS Type
1=On-Line, 2=Off-Line, 3=Line-Interactive, 4=Three Phase/Three phase, 5=Other, 10=Three-phase/Single phase.
ups_type4uint1611—R—