BTicino F4N200

Three-phase energy meter with LCD display. Registers from 5889 to 29923 not mapped.

Importata da documento

Mappa registri Modbus

159 registri

LenScalaEndian
10241
Restore default parameters
See Note 3
restore_default_parameters3uint1611R/W
257
Write Current transformer ratio - CT
CT = I prim / I sec ex: 500 A / 5 A  CT = 100
write_current_transformer_ratio_ct3uint1611R/W
259
Write Voltage transformer ratio - VT
VT = V prim / V sec ex: 600 V /100 V VT = 6.00  WRITE 600 --- If tranformer not present VT = 1.00  WRITE 100
write_voltage_transformer_ratio_vt3uint1611R/W
260
Energy mode accumulation
0: Asyn 1: Syn 2: Tariff 3: Pulse Counting
energy_mode_accumulation3uint1611R/W
769
Device identifier
The device returns 0006h
device_identifier3uint1611R
4097
Phase 1 : phase voltage
Measures
phase_1_phase_voltage3uint3221mVR
4099
Phase 2 : phase voltage
Measures
phase_2_phase_voltage3uint3221mVR
4101
Phase 3 : phase voltage
Measures
phase_3_phase_voltage3uint3221mVR
4103
Phase 1 : current
Measures
phase_1_current3uint3221mAR
4105
Phase 2 : current
Measures
phase_2_current3uint3221mAR
4107
Phase 3 : current
Measures
phase_3_current3uint3221mAR
4109
Neutral current
Measures
neutral_current3uint3221mAR
4111
Chained voltage : L1-L2
Measures
chained_voltage_l1_l23uint3221mVR
4113
Chained voltage : L2-L3
Measures
chained_voltage_l2_l33uint3221mVR
4115
Chained voltage : L3-L1
Measures
chained_voltage_l3_l13uint3221mVR
4117
3-phase : active power
See Note 1
3_phase_active_power3uint1611WR
4119
3-phase : reactive power
See Note 1
3_phase_reactive_power3uint1611varR
4121
3-phase : apparent power
See Note 1
3_phase_apparent_power3uint1611VAR
4123
3-phase : sign of active power
0=positive, 1=negative
3_phase_sign_of_active_power3uint1611R
4124
3-phase : sign of reactive power
0=positive, 1=negative
3_phase_sign_of_reactive_power3uint1611R
4125
3-phase : positive active energy
See Note 2
3_phase_positive_active_energy3uint1611WhR
4127
3-phase : positive reactive energy
See Note 2
3_phase_positive_reactive_energy3uint1611varhR
4129
3-phase : negative active energy
See Note 2
3_phase_negative_active_energy3uint1611WhR
4131
3-phase : negative reactive energy
See Note 2
3_phase_negative_reactive_energy3uint1611varhR
4133
3-phase : power factor
3_phase_power_factor3int1611R
4134
3-phase : sector of power factor (cap or ind)
0="PF=1", 1="ind" (L), 2="cap" (C)
3_phase_sector_of_power_factor_cap_or_ind3uint1611R
4135
Frequency
frequency3uint1611HzR
4136
3-phase : average power
See Note 1
3_phase_average_power3uint1611WR
4138
3-phase : peak maximum demand
See Note 1
3_phase_peak_maximum_demand3uint1611WR
4140
Time counter for average power
time_counter_for_average_power3uint1611minR
4141
Phase 1 : active power
See Note 1
phase_1_active_power3uint1611WR
4143
Phase 2 : active power
See Note 1
phase_2_active_power3uint1611WR
4145
Phase 3 : active power
See Note 1
phase_3_active_power3uint1611WR
4147
Phase 1 : sign of active power
0=positive, 1=negative
phase_1_sign_of_active_power3uint1611R
4148
Phase 2: sign of active power
0=positive, 1=negative
phase_2_sign_of_active_power3uint1611R
4149
Phase 3: sign of active power
0=positive, 1=negative
phase_3_sign_of_active_power3uint1611R
4150
Phase 1: reactive power
See Note 1
phase_1_reactive_power3uint3221varR
4152
Phase 2: reactive power
See Note 1
phase_2_reactive_power3uint3221varR
4154
Phase 3: reactive power
See Note 1
phase_3_reactive_power3uint3221varR
4156
Phase 1: sign of reactive power
0=positive, 1=negative
phase_1_sign_of_reactive_power3uint1611R
4157
Phase 2: sign of reactive power
0=positive, 1=negative
phase_2_sign_of_reactive_power3uint1611R
4158
Phase 3: sign of reactive power
0=positive, 1=negative
phase_3_sign_of_reactive_power3uint1611R
4159
Phase 1: apparent power
See Note 1
phase_1_apparent_power3uint3221VAR
4161
Phase 2: apparent power
See Note 1
phase_2_apparent_power3uint3221VAR
4163
Phase 3: apparent power
See Note 1
phase_3_apparent_power3uint3221VAR
4165
Phase 1: power factor
phase_1_power_factor3int1611R
4166
Phase 2: power factor
phase_2_power_factor3int1611R
4167
Phase 3: power factor
phase_3_power_factor3int1611R
4168
Phase 1: sector of power factor (cap or ind)
0="PF=1", 1="ind" (L), 2="cap" (C)
phase_1_sector_of_power_factor_cap_or_ind3uint1611R
4169
Phase 2: sector of power factor (cap or ind)
0="PF=1", 1="ind" (L), 2="cap" (C)
phase_2_sector_of_power_factor_cap_or_ind3uint1611R
4170
Phase 3: sector of power factor (cap or ind)
0="PF=1", 1="ind" (L), 2="cap" (C)
phase_3_sector_of_power_factor_cap_or_ind3uint1611R
4171
Phase 1: THD V1
See Note 4
phase_1_thd_v13uint1611%R
4172
Phase 2: THD V2
See Note 4
phase_2_thd_v23uint1611%R
4173
Phase 3: THD V3
See Note 4
phase_3_thd_v33uint1611%R
4174
Phase 1: THD I1
phase_1_thd_i13uint1611%R
4175
Phase 2: THD I2
phase_2_thd_i23uint1611%R
4176
Phase 3: THD I3
phase_3_thd_i33uint1611%R
4177
Phase 1: I1 average
phase_1_i1_average3uint3221mAR
4179
Phase 2: I2 average
phase_2_i2_average3uint3221mAR
4181
Phase 3: I3 average
phase_3_i3_average3uint3221mAR
4183
Phase 1: I1 peak Max.
phase_1_i1_peak_max3uint3221mAR
4185
Phase 2: I2 peak Max.
phase_2_i2_peak_max3uint3221mAR
4187
Phase 3: I3 peak Max.
phase_3_i3_peak_max3uint3221mAR
4189
3-phase: I average
(I1+I2+I3)/3
3_phase_i_average3uint3221mAR
4191
Phase 1: V1 min.
See Note 4
phase_1_v1_min3uint3221mVR
4193
Phase 2: V2 min.
See Note 4
phase_2_v2_min3uint3221mVR
4195
Phase 3: V3 min.
See Note 4
phase_3_v3_min3uint3221mVR
4197
Phase 1: V1 Max.
See Note 4
phase_1_v1_max3uint3221mVR
4199
Phase 2: V2 Max.
See Note 4
phase_2_v2_max3uint3221mVR
4201
Phase 3: V3 Max.
See Note 4
phase_3_v3_max3uint3221mVR
4203
3-phase: partial active energy
See Note 2
3_phase_partial_active_energy3uint3221WhR
4205
3-phase: partial reactive energy
See Note 2
3_phase_partial_reactive_energy3uint3221varhR
4207
Operating timer counter
operating_timer_counter3uint1611hR
4208
Alarm status | Output Remote Command
0: No active alarm, 1: Alarm active | 0: Deactivate 1: Activate
alarm_status_output_remote_command3uint1611R/W
4209
3-phase: average active power
See Note 1
3_phase_average_active_power3uint3221WR
4211
3-phase: average reactive power
See Note 1
3_phase_average_reactive_power3uint3221varR
4213
3-phase: average apparent power
See Note 1
3_phase_average_apparent_power3uint3221VAR
4215
3-phase: active PMD power
See Note 1
3_phase_active_pmd_power3uint3221WR
4217
3-phase: reactive PMD power
See Note 1
3_phase_reactive_pmd_power3uint3221varR
4219
3-phase: apparent PMD power
See Note 1
3_phase_apparent_pmd_power3uint3221VAR
4609
Current transformer ratio (CT)
current_transformer_ratio_ct3uint1611R
4610
Voltage transformer ratio (VT)
voltage_transformer_ratio_vt3uint1611R
4615
Digital Inputs Status
See Note 3
digital_inputs_status3uint1611R
4689
3-phase: Positive total active energy
3-phase: Positive total active energy
3_phase_positive_total_active_energy3uint3221WhR
4691
3-phase: Positive total reactive energy
See Note 2
3_phase_positive_total_reactive_energy3uint3221varhR
4693
3-phase: Negative total active energy
See Note 2
3_phase_negative_total_active_energy3uint3221WhR
4695
3-phase: Negative total reactive energy
See Note 2
3_phase_negative_total_reactive_energy3uint3221varhR
4697
3-phase Positive partial active energy or tariff 1 active energy (if option tariffs)
See Note 2
3_phase_positive_partial_active_energy_or_tariff_1_active_energy_if_option_tariffs3uint3221WhR
4699
3-phase Negative partial active energy or tariff 2 active energy (if option tariffs)
See Note 2
3_phase_negative_partial_active_energy_or_tariff_2_active_energy_if_option_tariffs3uint3221WhR
4701
3-phase Positive partial reactive energy or tariff 3 active energy (if option tariffs)
See Note 2
3_phase_positive_partial_reactive_energy_or_tariff_3_active_energy_if_option_tariffs3uint3221WhR
4703
3-phase Negative partial reactive energy or tariff 4 active energy (if option tariffs)
See Note 2
3_phase_negative_partial_reactive_energy_or_tariff_4_active_energy_if_option_tariffs3uint3221varhR
4865
3-phase: active average power
See Note 1
3_phase_active_average_power3uint3221WR
4867
3-phase: reactive average power
See Note 1
3_phase_reactive_average_power3uint3221varR
4869
3-phase : apparent average power
See Note 1
3_phase_apparent_average_power3uint1611VAR
4871
3-phase : active average power tarifs 1
See Note 1
3_phase_active_average_power_tarifs_13uint1611WR
4873
3-phase : reactive average power tarifs 1
See Note 1
3_phase_reactive_average_power_tarifs_13uint1611varR
4875
3-phase : apparent average power tarifs 1
See Note 1
3_phase_apparent_average_power_tarifs_13uint1611VAR
4877
3-phase : active average power tarifs 2
See Note 1
3_phase_active_average_power_tarifs_23uint1611WR
4879
3-phase : reactive average power tarifs 2
See Note 1
3_phase_reactive_average_power_tarifs_23uint1611varR
4881
3-phase : apparent average power tarifs 2
See Note 1
3_phase_apparent_average_power_tarifs_23uint1611VAR
4883
3-phase : active average power tarifs 3
See Note 1
3_phase_active_average_power_tarifs_33uint1611WR
4885
3-phase : reactive average power tarifs 3
See Note 1
3_phase_reactive_average_power_tarifs_33uint1611varR
4887
3-phase : apparent average power tarifs 3
See Note 1
3_phase_apparent_average_power_tarifs_33uint1611VAR
4889
3-phase : active average power tarifs 4
See Note 1
3_phase_active_average_power_tarifs_43uint1611WR
4891
3-phase : reactive average power tarifs 4
See Note 1
3_phase_reactive_average_power_tarifs_43uint1611varR
4893
3-phase : apparent average power tarifs 4
See Note 1
3_phase_apparent_average_power_tarifs_43uint1611VAR
5425
Total Apparent power
total_apparent_power3uint1611VAR
5427
3-phase : average active power
3_phase_average_active_power_54273uint1611WR
5429
3-phase : average reactive power
3_phase_average_reactive_power_54293uint1611varR
5431
3-phase : average apparent power
3_phase_average_apparent_power_54313uint1611VAR
5433
3-phase : max active power
3_phase_max_active_power3uint1611WR
5435
3-phase : max reactive power
3_phase_max_reactive_power3uint1611varR
5437
3-phase : max apparent power
3_phase_max_apparent_power3uint1611VAR
5505
Phase1 voltage crest factor
phase1_voltage_crest_factor3uint1611R
5506
Phase2 voltage crest factor
phase2_voltage_crest_factor3uint1611R
5507
Phase3 voltage crest factor
phase3_voltage_crest_factor3uint1611R
5508
Phase1 current crest factor
phase1_current_crest_factor3uint1611R
5509
Phase2 current crest factor
phase2_current_crest_factor3uint1611R
5510
Phase3 current crest factor
phase3_current_crest_factor3uint1611R
5511
Phase1-2 voltage crest factor
phase1_2_voltage_crest_factor3uint1611R
5512
Phase2-3 voltage crest factor
phase2_3_voltage_crest_factor3uint1611R
5513
Phase3-1 voltage crest factor
phase3_1_voltage_crest_factor3uint1611R
5633
phase displacement V1-V2 (V12-V23)
See Note 4
phase_displacement_v1_v2_v12_v233uint1611°R
5634
phase displacement V2-V3 (V23-V31)
See Note 4
phase_displacement_v2_v3_v23_v313uint1611°R
5635
phase displacement V3-V1 (V31-V12)
See Note 4
phase_displacement_v3_v1_v31_v123uint1611°R
5636
phase displacement I1-I2
phase_displacement_i1_i23uint1611°R
5637
phase displacement I2-I3
phase_displacement_i2_i33uint1611°R
5638
phase displacement I3-I1
phase_displacement_i3_i13uint1611°R
5639
phase displacement V1-I1
phase_displacement_v1_i13uint1611°R
5640
phase displacement V2-I2
phase_displacement_v2_i23uint1611°R
5641
phase displacement V3-I3
phase_displacement_v3_i33uint1611°R
5642
phase displacement total
phase_displacement_total3uint1611°R
8193
Standard Setup parameters
write 16 byte at once
standard_setup_parameters3uint1611R/W
8197
Percentage of rated 3phase active power run hour meter
50 ÷ 5000 means (0.5% ÷ 50.00%)
percentage_of_rated_3phase_active_power_run_hour_meter3uint1611%R/W
8198
Run hour meter active on
0: Voltages, 1 Power
run_hour_meter_active_on3uint1611R/W
8201
Backlight intensity
0: 0% 1: 35% 2: 70% 3: 100%
backlight_intensity3uint1611R/W
8203
Power Averaging time
0: 5min 1: 8min 2: 10min 3: 15min 4: 20min 5: 30min 6: 60min
power_averaging_time3uint1611R/W
8204
Insertion type
0: 3N-3E 1: 3-3E 2: 3-2E 3: 1N-1E 4: 3N-1E 5: 3-1E
insertion_type3uint1611R/W
8205
Measure on line 1 of custom page
0:V1 1:V12 2:I1 3:In 4:P 5:Q 6:S 7:P1 8:Q1 9:S1 10:PF 3-phase
measure_on_line_1_of_custom_page3uint1611R/W
8206
Measure on line 2 of custom page
0:V2 1:V23 2:I2 3:P 4:Q 5:S 6:P2 7:Q2 8:S2 9:Freq 10:I1
measure_on_line_2_of_custom_page3uint1611R/W
8207
Measure on line 3 of custom page
0:V3 1:V31 2:I3 3:P 4:Q 5:S 6:P3 7:Q3 8:S3 9:P1 10:I1
measure_on_line_3_of_custom_page3uint1611R/W
8705
Output option Setup parameters
write 24 byte at once
output_option_setup_parameters3uint1611R/W
8715
W10 Output type
0: Pulse out 1: Alarm out 2: Dual stable Remote command 3: Timed Remote command
w10_output_type3uint1611R/W
8716
W11 Pulse duration
0: 50 ms 1: 100 ms 2: 200 ms 3: 300 ms 4: 400 ms 5: 500ms
w11_pulse_duration3uint1611R/W
8717
W12 Pulse weight
0: 0.01 kWh 1: 0.10 kWh 2: 1.00 kWh 3: 10.0 kWh 4: 0.10 MWh 5: 1.00 MWh 6: 10.0 MWh
w12_pulse_weight3uint1611R/W
8718
W13 Pulse active on
0: Active Energy 1: Reactive Energy
w13_pulse_active_on3uint1611R/W
8719
W14 Alarm deactivation delay or Relay closing time
if Output type = Timed Remote command
w14_alarm_deactivation_delay_or_relay_closing_time3uint1611sR/W
8720
W15 Alarm activation delay
w15_alarm_activation_delay3uint1611sR/W
8721
W16 Hysteresis
w16_hysteresis3uint1611%R/W
8722
W17 Relay (NO/NC)
0: NO 1: NC
w17_relay_no_nc3uint1611R/W
8723
W18 Alarm on Min Value or Max Value
0: Min 1: Max
w18_alarm_on_min_value_or_max_value3uint1611R/W
8724
W19 Alarm setpoint
w19_alarm_setpoint3uint1611R/W
8725
W20
w203uint1611R/W
8726
W21 Unit of setpoint
0: X.XXX 1: XX.XX 2: XXX.X 3: X.XXX k 4: XX.XX k 5: XXX.X k 6: X.XXX M 7: XX.XX M 8: XXX.X M
w21_unit_of_setpoint3uint1611R/W
8727
W22 Sign of Alarm setpoint
0: '+' 1: '-'
w22_sign_of_alarm_setpoint3uint1611R/W
8728
W23 Type of measure
0:V1 1:V2 2:V3 3:V12 4:V23 5:V31 6:I1 7:I2 8:I3 9:Freq 10:Active Power 11:Reactive Power
w23_type_of_measure3uint1611R/W
9217
Reset parameters
See Note 1
reset_parameters3uint1611R/W
9729
Saving parameters
See Note 2
saving_parameters3uint1611R/W
9985
Enable writing
See Note 2 & Note 3
enable_writing3uint1611R/W