abb TRIO-50.0/60.0-TL-OUTD
TRIO-50.0/60.0-TL-OUTD
Importata da documento
| Len | Scala | Endian | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| 180 | Remote On/Off 0=Remote ON, 1=Remote OFF. Eseguito solo se la funzione 'Remote on/off' e' abilitata nell'inverter (non tramite Modbus). | remote_on_off | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 181 | Remove 'Reset by Hand' latch-state Scrivere 1 per rimuovere lo stato di latch pendente; il registro si azzera automaticamente. Il reset automatico al ripristino rete e' disponibile di default solo per la normativa Giapponese. | remove_reset_by_hand_latch_state | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 190 | Transient Time (Blocco 1 - Backward compatibility) Governa i comandi ai registri 200,202,210,212,220,222,225,227. Default 4. Vedi Annex 9 per la formula di codifica (N=multiplo di Transient Step, M=centesimi di secondo). | transient_time_blocco_1_backward_compatibility | 3 | uint16 | 1 | 1 | s | R/W | — | |
| 191 | Timeout Dynamic Mode (Blocco 1) 0-250, default 2. Timer di conto alla rovescia per i comandi Dynamic Mode (200,210,220,225). | timeout_dynamic_mode_blocco_1 | 3 | uint16 | 1 | 1 | min | R/W | — | |
| 198 | Transient Options (Blocco 1) 0/128/256/384, default 256. MSB=Transient Step (0=step 4s,1=step 1s), LSB=Smooth Mode (0=Slope,1=Time). Vedi Annex 8. | transient_options_blocco_1 | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 200 | Dynamic Mode - Power Factor Set Point -1..-0.001 o 0.001..1, default 0. Negativo=over-excited (capacitivo), positivo=under-excited (induttivo). Usare con registri 190,191,198. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | dynamic_mode_power_factor_set_point | 3 | float32 | 2 | 1 | — | R/W | — | |
| 202 | Permanent Mode - Power Factor Set Point -1..-0.001 o 0.001..1, default 1. Stessa convenzione di segno di 200. Usare con registri 190,191,198. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | permanent_mode_power_factor_set_point | 3 | float32 | 2 | 1 | — | R/W | — | |
| 205 | Reset Reactive Power / Power Factor (Blocco 1) Scrivere 1 per forzare il reset a zero (PF=1); il registro si azzera automaticamente. | reset_reactive_power_power_factor_blocco_1 | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 210 | Dynamic Mode - Active Power % 0-100, default 100, passi 1%. Usare con registri 190,191,198. | dynamic_mode_active_power | 3 | uint16 | 1 | 1 | % | R/W | — | |
| 212 | Permanent Mode - Active Power % 0-100, default 100, passi 1%. Usare con registri 190,191,198. | permanent_mode_active_power | 3 | uint16 | 1 | 1 | % | R/W | — | |
| 215 | Reset Active Power management (Blocco 1) Scrivere 1 per forzare il reset alla Potenza Nominale; il registro si azzera automaticamente. | reset_active_power_management_blocco_1 | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 220 | Dynamic Mode - Reactive Power (rapporto su potenza apparente max) -1.0..1.0, default 0. Negativo=over-excited, positivo=under-excited. Usare con registri 190,191,198. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | dynamic_mode_reactive_power_rapporto_su_potenza_apparente_max | 3 | float32 | 2 | 1 | — | R/W | — | |
| 222 | Permanent Mode - Reactive Power (rapporto su potenza apparente max) -1.0..1.0, default 0. Usare con registri 190,191,198. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | permanent_mode_reactive_power_rapporto_su_potenza_apparente_max | 3 | float32 | 2 | 1 | — | R/W | — | |
| 225 | Dynamic Mode - Reactive Power % di potenza apparente max -100..100, default 0. Negativo=over-excited, positivo=under-excited. Usare con registri 190,191,198. | dynamic_mode_reactive_power_di_potenza_apparente_max | 3 | int16 | 1 | 1 | % | R/W | — | |
| 227 | Permanent Mode - Reactive Power % di potenza apparente max -100..100, default 0. Usare con registri 190,191,198. | permanent_mode_reactive_power_di_potenza_apparente_max | 3 | int16 | 1 | 1 | % | R/W | — | |
| 300 | Heartbeat counter Incrementa ogni secondo, si azzera automaticamente a 65535. | heartbeat_counter | 3 | uint16 | 1 | 1 | s | R | — | |
| 301 | Inverter-Grid Reactive Power (mirror) Sola lettura. Se la misura di potenza reattiva non e' supportata ritorna 0xFFFFFFFF. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | inverter_grid_reactive_power_mirror | 3 | float32 | 2 | 1 | VAr | R | — | |
| 303 | Inverter-Grid Voltage (mirror) Sola lettura. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | inverter_grid_voltage_mirror | 3 | float32 | 2 | 1 | V | R | — | |
| 305 | Inverter-Grid Active Power (mirror) Sola lettura. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | inverter_grid_active_power_mirror | 3 | float32 | 2 | 1 | W | R | — | |
| 307 | Inverter-Grid Current (mirror) Sola lettura. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | inverter_grid_current_mirror | 3 | float32 | 2 | 1 | A | R | — | |
| 501 | Accuracy (unita' registri 507/508/511/512) 0=per mille (‰), 1=percento (%). | accuracy_unita_registri_507_508_511_512 | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 502 | Set active mode (Blocco 2 - Plant controller) 0=Dynamic mode, 1=Permanent mode. | set_active_mode_blocco_2_plant_controller | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 503 | Transient Time (Blocco 2) Governa i comandi ai registri 507,508,509,511,512,513. Default 4. Vedi Annex 9. | transient_time_blocco_2 | 3 | uint16 | 1 | 1 | s | R/W | — | |
| 504 | Timeout Dynamic Mode (Blocco 2) 0-250, default 2. | timeout_dynamic_mode_blocco_2 | 3 | uint16 | 1 | 1 | min | R/W | — | |
| 505 | Transient Options (Blocco 2) 0/128/256/384, default 256. Vedi Annex 8. | transient_options_blocco_2 | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 506 | Reactive Power control mode (Blocco 2) 0=PF fixed mode, 1=Q fixed mode. | reactive_power_control_mode_blocco_2 | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 507 | Dynamic Mode - Reactive Power % (Blocco 2) -100..100 (% o ‰ secondo registro 501), default 0. Usare con 501,502,503,504,505,506. | dynamic_mode_reactive_power_blocco_2 | 3 | int16 | 1 | 1 | % | R/W | — | |
| 508 | Dynamic Mode - Active Power % (Blocco 2) 0-100 o 0-1000 secondo registro 501, default 1000. Usare con 501,502,503,504,505. | dynamic_mode_active_power_blocco_2 | 3 | uint16 | 1 | 1 | ‰ | R/W | — | |
| 509 | Dynamic Mode - Power Factor Set Point (Blocco 2) -1.0..1.0, default 1. Usare con 501,502,503,504,505,506. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | dynamic_mode_power_factor_set_point_blocco_2 | 3 | float32 | 2 | 1 | — | R/W | — | |
| 511 | Permanent Mode - Reactive Power % (Blocco 2) -100..100 (% o ‰), default 0. Usare con 501-506. | permanent_mode_reactive_power_blocco_2 | 3 | int16 | 1 | 1 | % | R/W | — | |
| 512 | Permanent Mode - Active Power % (Blocco 2) 0-100 o 0-1000, default 1000. Usare con 501,502,503,504,505. | permanent_mode_active_power_blocco_2 | 3 | uint16 | 1 | 1 | ‰ | R/W | — | |
| 513 | Permanent Mode - Power Factor Set Point (Blocco 2) -1.0..1.0, default 1. Usare con 501-506. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | permanent_mode_power_factor_set_point_blocco_2 | 3 | float32 | 2 | 1 | — | R/W | — | |
| 515 | Reset Active Power management (Blocco 2) Scrivere 1 per forzare il reset alla Potenza Nominale. | reset_active_power_management_blocco_2 | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 516 | Reset Reactive Power / PF management (Blocco 2) Scrivere 1 per forzare il reset a zero (PF=1). | reset_reactive_power_pf_management_blocco_2 | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 801 | Enable/Disable 'Reset by Hand' 0=Disabilita, 1=Abilita (default). | enable_disable_reset_by_hand | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 802 | Remove 'Reset by Hand' latch-state (alt.) Equivalente al registro 181, nessuna differenza funzionale. | remove_reset_by_hand_latch_state_alt | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 1000 | Inverter ID Valore fisso 261. | inverter_id | 4 | uint16 | 1 | 1 | — | R | — | |
| 1001 | Inverter Block Modbus Map size Valore fisso 132. | inverter_block_modbus_map_size | 4 | uint16 | 1 | 1 | — | R | — | |
| 1002 | Inverter Presence 1=dispositivo presente. | inverter_presence | 4 | uint16 | 1 | 1 | — | R | — | |
| 1003 | Inverter Part number DIM=6 (ASCII), valore fisso '-3N63-'. | inverter_part_number | 4 | string | — | 1 | — | R | — | |
| 1006 | Set comm. protocol RS485 #1 0=Aurora, 1=Modbus (default). Il cambio protocollo e' immediato, subito dopo la risposta Modbus. | set_comm_protocol_rs485_1 | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 1007 | Set comm. protocol RS485 #2 0=Aurora, 1=Modbus (default). Cambio immediato dopo la risposta. | set_comm_protocol_rs485_2 | 3 | uint16 | 1 | 1 | — | R/W | — | |
| 1009 | Inverter Serial number DIM=6 (ASCII). | inverter_serial_number | 4 | string | — | 1 | — | R | — | |
| 1015 | Inverter Manufacture date (Settimana) DIM=2 (ASCII). | inverter_manufacture_date_settimana | 4 | string | — | 1 | — | R | — | |
| 1017 | Inverter Manufacture date (Anno) DIM=2 (ASCII). Valore registro = anno di fabbricazione - 2000. | inverter_manufacture_date_anno | 4 | string | — | 1 | — | R | — | |
| 1019 | Inverter Type 78="N" (Photovoltaic Inverter Type), 87="W" (Wind Inverter Type). Codificato come carattere ASCII (Annex 1). | inverter_type | 4 | uint16 | 1 | 1 | — | R | — | |
| 1020 | Grid Type Codificato come carattere ASCII (Annex 2). 65="A" UL1741; 66="B" Netherlands; 67="C" Czech Republic; 68="D" Canada; 69="E" VDE 0126; 70="F" France LL 2013; 71="G" Greece; 72="H" Hungary; 73="I" ENEL Guida; 74="J" CEI-016; 75="K" AS-4777; 76="L" Thailand PEA; 77="M" BG C10-11 110%; 78="N" Romania; 79="O" Korea; 80="P" Portugal; 81="Q" China HV; 82="R" Ireland; 83="S" Spain RD 1699; 84="T" Taiwan; 87="W" BDEW; 88="X" DEBUG FF; 89="Y" Turkey HV; 90="Z" Brazil; 100="d" France LL 2014; 101="e" VDE 4105; 103="g" JP 50Hz 400V; 104="h" JP 60Hz 400V; 106="j" CEI021 EX; 107="k" Israel; 108="l" Singapore; 109="m" BG C10-11 100%; 110="n" EN 50438; 111="o" Corsica; 112="p" Spain RD 1565; 113="q" China LV; 114="r" South Africa; 115="s" Slovenia; 116="t" Turkey LV; 117="u" UK G59; 119="w" VDE 0126 3W; 120="x" DEBUG 88; 121="y" Thailand MEA. | grid_type | 4 | uint16 | 1 | 1 | — | R | — | |
| 1021 | Transformer Type DIM=1 (ASCII). Es. 'N' = Transformerless. | transformer_type | 4 | string | — | 1 | — | R | — | |
| 1022 | Model Type Codificato come carattere ASCII (Annex 14). 40="(" TRIO-50-TL-OUTD-EU; 47="/" TRIO-60-TL-OUTD; 41=")" TRIO-50-TL-OUTD-US; 58=":" TRIO-60-TL-OUTD-US; 59=";" TRIO-50-TL-OUTD-JP E TRIO-TM-50.0-400 (stesso codice per entrambi nel documento originale); 92="\" TRIO-TM-60.0-480. | model_type | 4 | uint16 | 1 | 1 | — | R | — | |
| 1050 | Global State Vedi Annex 3. 0="Initializing (configuring power control)",1="Waiting sun or grid",2="Connecting to grid (checking grid)",3="Initializing (system startup)",4="Connecting to grid (switching-on DC/DC)",5="Connecting to grid (switching-on DC/AC)",6="Connected to grid (Run: unico stato in cui l'inverter puo' esportare potenza in rete)",7="Post-alarm actions (recovery)",8="Post-alarm actions (pause)",9="Ground fault",10="Over-temperature fault",12="Connecting to grid (grid protection interface self-test)",13="Grid protection interface self-test fault",14="Connecting to grid (safety checks)",15="Leakage fault",24="Under-temperature fault",25="Interlock (remote off)",26="Interlock (emergency stop)",27="Executing auto-test",29="Grounding-kit fault",30="SW bundle not valid fault",41="Temperature sensors fault",42="Grid sequence fault",51="Arc fault",53="Arc detector self-test fault",116="Power stage off-line",118="Arc detector wrong configuration fault",119="Arc detector self-test",120="Configuration fault (bad model)",124="Latch with Reset by hand",150="Power stage communication fault",151="Configuration fault (bad global-settings)",200="Programming power stage". | global_state | 4 | uint16 | 1 | 1 | — | R | — | |
| 1051 | Alarm State Vedi Annex 4 (valore integer -> codice allarme). 0=NONE(No alarm); 2=E001(Input OC); 3=W002(Input UV); 4=E002(Input OV); 6=E003(No pars DSP); 7=E004(Bulk OV); 8=E005(Internal error); 9=E006(Output OC); 10=E007(IGBT sat.); 11=W011(Bulk UV); 14=E010(Bulk UV); 15=E011(Ramp Fault); 16=E012(Internal error); 17=E013(Wrong input mode, non disponibile su TRIO-50/60-TL); 19=E014(Over temperature); 20=E015(Cap. Fault); 21=E016(Internal error); 22=E017(Internal error); 23=E018(Leak fault); 24=E049(Internal error); 25=E019(Internal error); 26=E012(Internal error); 27=E020(Internal error); 28=E021(Internal error); 29=E019(Internal error); 30=E022(Internal error); 31=E023(DC injection); 38=E025(Riso low); 42=E029(Mid bulk OV); 44=E031(Internal error); 45=E032(Internal error); 48=E033(Undertemperature); 49=E034(IGBT not ready); 50=E035(Remote Off); 51=E036(Internal error); 54=E037(Riso low); 62=W015(Island. Detected); 78=E078(Riso Test Fail); 79=E050(AFDD activated); 82=E053(AFDD fault); 85=E055(AFDD wrong conf.); 90=W048(Periodic Grid Off); 91=E077(Internal error); 95=W046(Grid conn. fault); 96=E075(Latch-Manual ent); 150=W047(Update Incomplete); 152=E079(Wrong Sequence); 156=E084(BackFeed OC); 167=E098(Aux. Bulk Feed Conn. Error, non disponibile su TRIO-50/60-TL); 170=E099(Ground Kit Self Test Error, non disponibile su TRIO-50/60-TL). Nota: i codici E012 e E019 compaiono due volte su valori diversi nel documento originale, preservato verbatim. | alarm_state | 4 | uint16 | 1 | 1 | — | R | — | |
| 1052 | DC/DC Converter State Solo per debug (nessuna informazione utile per il monitoraggio, vedi Global/Alarm/Derating State). Vedi Annex 5. 1="Ramp",2="MPPT",4="Input over-current",5="Input under-voltage",6="Input over-voltage",7="Low input",8="No configuration",9="Bulk under-voltage",10="Communication error",11="Ramp fault",12="Pending redundancy fault",13="Wrong input mode",14="Ground fault",15="Pending redundancy fault",16="IGBT error",17="Leakage sensor self-test fault",18="Grid fault",19="Communication error",20="Charging bulk",21="IGBT not ready",255="Not programmed". | dc_dc_converter_state | 4 | uint16 | 1 | 1 | — | R | — | |
| 1053 | DC/AC Converter State Solo per debug. Vedi Annex 6. 0="Initializing",1="Connecting to grid",2="Connected to grid",3="Bulk over-voltage",4="Output over-current",5="IGBT fault",6="Bulk under-voltage",7="Leakage sensor degaussing error",8="No configuration",9="Low bulk voltage",10="Grid fault",11="Communication error",12="Leakage sensor degaussing error",13="Connecting to grid",14="Bulk capacitor fault",15="Leakage fault",16="Pending redundancy fault",17="Leakage sensor self-test fault",18="Grid protection self-test",19="Leakage sensor self-test",20="Grid protection self-test",21="Grid protection self-test",22="Grid protection self-test timeout",23="Grid protection self-test fault",24="Grid protection self-test fault",25="Auto-test",30="Grid voltage read error",31="Grid current read error",33="IGBT not ready",35="Communication error",36="Mid-bulk over-voltage",255="Not programmed". | dc_ac_converter_state | 4 | uint16 | 1 | 1 | — | R | — | |
| 1054 | Derating State Bitmask (Annex 7); piu' derating possono essere attivi insieme, in tal caso la potenza e' limitata al minimo tra i limiti attivi. bit0=Power curtailment from user setpoint; bit1=Grid over-frequency derating; bit2=Average grid over-voltage derating; bit3=Anti-islanding derating; bit4=Nameplate grid current limitation; bit5=Over-temperature derating; bit6=DC over-voltage derating; bit7=Energy storage system zero-Power injection. | derating_state | 4 | bitfield | 1 | 1 | — | R | — | |
| 1070 | Daily Energy | daily_energy | 4 | uint32 | 2 | 1 | Wh | R | — | |
| 1072 | Total Energy | total_energy | 4 | uint32 | 2 | 1 | Wh | R | — | |
| 1074 | Partial Energy | partial_energy | 4 | uint32 | 2 | 1 | Wh | R | — | |
| 1076 | Weekly Energy | weekly_energy | 4 | uint32 | 2 | 1 | Wh | R | — | |
| 1078 | Monthly Energy | monthly_energy | 4 | uint32 | 2 | 1 | Wh | R | — | |
| 1080 | Yearly Energy | yearly_energy | 4 | uint32 | 2 | 1 | Wh | R | — | |
| 1090 | Mean Grid Voltage (Phase to Neutral) Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | mean_grid_voltage_phase_to_neutral | 4 | float32 | 2 | 1 | V | R | — | |
| 1092 | Mean Output Current (Phase to Neutral) Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | mean_output_current_phase_to_neutral | 4 | float32 | 2 | 1 | A | R | — | |
| 1094 | Output Active Power: Instantaneous Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | output_active_power_instantaneous | 4 | float32 | 2 | 1 | W | R | — | |
| 1096 | Output Active Power: Absolute Peak Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | output_active_power_absolute_peak | 4 | float32 | 2 | 1 | W | R | — | |
| 1098 | Output Active Power: Daily Peak Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | output_active_power_daily_peak | 4 | float32 | 2 | 1 | W | R | — | |
| 1100 | Output Active Power: Feedback on Curtailment applied Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | output_active_power_feedback_on_curtailment_applied | 4 | float32 | 2 | 1 | W | R | — | |
| 1102 | Reactive Power: Feedback on Set Point applied Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | reactive_power_feedback_on_set_point_applied | 4 | float32 | 2 | 1 | VAr | R | — | |
| 1104 | Power Factor: Feedback on Set Point applied Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | power_factor_feedback_on_set_point_applied | 4 | float32 | 2 | 1 | — | R | — | |
| 1106 | Mean Grid Frequency Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | mean_grid_frequency | 4 | float32 | 2 | 1 | Hz | R | — | |
| 1108 | Active Power on DC Input #1 Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | active_power_on_dc_input_1 | 4 | float32 | 2 | 1 | W | R | — | |
| 1110 | Voltage on DC Input #1 Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | voltage_on_dc_input_1 | 4 | float32 | 2 | 1 | V | R | — | |
| 1112 | Current on DC Input #1 Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | current_on_dc_input_1 | 4 | float32 | 2 | 1 | A | R | — | |
| 1114 | Active Power on DC Input #2 Solo per varianti TRIO-TM (3 MPPT). Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | active_power_on_dc_input_2 | 4 | float32 | 2 | 1 | W | R | — | |
| 1116 | Voltage on DC Input #2 Solo per varianti TRIO-TM. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | voltage_on_dc_input_2 | 4 | float32 | 2 | 1 | V | R | — | |
| 1118 | Current on DC Input #2 Solo per varianti TRIO-TM. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | current_on_dc_input_2 | 4 | float32 | 2 | 1 | A | R | — | |
| 1120 | Internal Temperature (DC Box) Il tempo di aggiornamento puo' essere leggermente piu' lungo rispetto agli altri parametri. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | internal_temperature_dc_box | 4 | float32 | 2 | 1 | °C | R | — | |
| 1122 | Inverter Temperature (DC/AC Converter) Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | inverter_temperature_dc_ac_converter | 4 | float32 | 2 | 1 | °C | R | — | |
| 1126 | Isolation Resistance Valore rilevato all'avvio. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | isolation_resistance | 4 | float32 | 2 | 1 | MΩ | R | — | |
| 1128 | Max Leakage Current Corrente di dispersione massima in caso di guasto verso terra. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | max_leakage_current | 4 | float32 | 2 | 1 | A | R | — | |
| 1130 | Active Power on DC Input #3 Solo per varianti TRIO-TM. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | active_power_on_dc_input_3 | 4 | float32 | 2 | 1 | W | R | — | |
| 1132 | Voltage on DC Input #3 Solo per varianti TRIO-TM. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | voltage_on_dc_input_3 | 4 | float32 | 2 | 1 | V | R | — | |
| 1134 | Current on DC Input #3 Solo per varianti TRIO-TM. Formato SF32 (Word Swapped Floating Point): IEEE754 a 32 bit con le due parole scambiate rispetto all'ordine standard (parola bassa trasmessa per prima). | current_on_dc_input_3 | 4 | float32 | 2 | 1 | A | R | — | |
| 3650 | Modbus Map - Family product Valore fisso 'G' (ASCII). | modbus_map_family_product | 4 | string | — | 1 | — | R | — | |
| 3651 | Modbus Map - Product model Valore fisso 't' (ASCII). | modbus_map_product_model | 4 | string | — | 1 | — | R | — | |
| 3652 | Modbus Map - Major release Valore fisso '3' (ASCII). | modbus_map_major_release | 4 | string | — | 1 | — | R | — | |
| 3653 | Modbus Map - Minor release Valore fisso '0' (ASCII). | modbus_map_minor_release | 4 | string | — | 1 | — | R | — | |
| 3654 | Modbus Map - Build version | modbus_map_build_version | 4 | uint16 | 1 | 1 | — | R | — |